Learn PLCs free
Intermediate20 min readProcess Control

Inovance Structured Text for Temperature Control

Learn Structured Text programming for Temperature Control using Inovance InoProShop / AutoShop. Includes code examples, best practices, and step-by-step implementation guide for Process Control applications.

💻
Platform
InoProShop / AutoShop
📊
Complexity
Intermediate
⏱️
Project Duration
2-3 weeks

Learning to implement Structured Text for Temperature Control using Inovance's InoProShop / AutoShop is a useful skill for PLC programmers working in Process Control. This guide walks through the fundamentals with clear explanations and an illustrative example that you can adapt to a simulator or test bench.

The example uses Inovance terminology and references controller families such as AM600 and AM610. Confirm the exact instructions, data types, firmware requirements, and licensing in the current vendor documentation before choosing hardware or deploying a project.

The Structured Text approach is particularly well-suited for Temperature Control because complex calculations, data manipulation, advanced control algorithms, and when code reusability is important. This combination allows you to leverage powerful for complex logic while managing the typical challenges of Temperature Control, including pid tuning and temperature stability.

Throughout this guide, you'll find step-by-step implementation guidance, an illustrative code example, and a verification checklist specific to Process Control. Whether you're programming your first Temperature Control exercise or transitioning from another PLC platform, use the material as a starting point and validate it in your exact InoProShop / AutoShop version and controller environment.

Inovance InoProShop / AutoShop for Temperature Control

InoProShop / AutoShop is a programming environment associated with Inovance controller families such as AM600, AM610, H5U. This guide uses Structured Text terminology from the supplied guide dataset, but controller capabilities and language support can change by model, firmware, software edition, and license.

Verify Before You Start:

  • The selected controller supports the required Structured Text constructs

  • The project version matches the installed InoProShop / AutoShop release

  • Required communications, motion, safety, and simulation options are licensed

  • Firmware and device-description files are compatible with the project

  • The vendor manuals used for the design match the exact hardware revision


Application Planning:

For a Temperature Control exercise, map the required inputs and outputs before writing logic. The example considers 4 sensor types, including Thermocouples (K-type, J-type), RTD sensors (PT100, PT1000), Infrared temperature sensors, and 5 actuator types.

Control Equipment for Temperature Control:

  • Electric resistance heaters (cartridge, band, strip)

  • Steam injection systems

  • Thermal fluid (hot oil) systems

  • Refrigeration and chiller systems


Controller-family references used in this guide include:

  • AM600: Confirm CPU, I/O, memory, communications, and Structured Text support in the current selection guide

  • AM610: Confirm CPU, I/O, memory, communications, and Structured Text support in the current selection guide

  • H5U: Confirm CPU, I/O, memory, communications, and Structured Text support in the current selection guide

  • AC800: Confirm CPU, I/O, memory, communications, and Structured Text support in the current selection guide


Hardware Selection Checklist:

  • Count local and remote I/O, including planned expansion

  • Measure the required task and communications update rates

  • Identify memory, data-retention, diagnostics, and cybersecurity requirements

  • Treat safety functions as a separate, standards-led design activity

  • Confirm lifecycle status, regional availability, licensing, and support


Source and Validation Note:

This page does not represent a vendor certification or a hardware acceptance test. Use current Inovance manuals, release notes, and safety documentation as the authority for product-specific behavior. Validate adapted logic in a simulator or isolated test setup before connecting it to equipment.

Investment Considerations:

For Temperature Control projects, compare hardware, software licensing, training, engineering, test equipment, commissioning, spares, and ongoing support. Obtain current pricing and lifecycle information directly from the vendor or an authorized regional supplier.

Understanding Structured Text for Temperature Control

Structured Text (ST) is a high-level, text-based programming language defined in IEC 61131-3. It resembles Pascal and provides powerful constructs for complex algorithms, calculations, and data manipulation.

Execution Model:

Code executes sequentially from top to bottom within each program unit. Variables maintain state between scan cycles unless explicitly reset.

Core Advantages for Temperature Control:

  • Powerful for complex logic: Critical for Temperature Control when handling intermediate control logic

  • Excellent code reusability: Critical for Temperature Control when handling intermediate control logic

  • Compact code representation: Critical for Temperature Control when handling intermediate control logic

  • Good for algorithms and calculations: Critical for Temperature Control when handling intermediate control logic

  • Familiar to software developers: Critical for Temperature Control when handling intermediate control logic


Why Structured Text Fits Temperature Control:

Temperature Control systems in Process Control typically involve:

  • Sensors: RTDs (PT100/PT1000) for high-accuracy measurements, Thermocouples (J, K, T types) for high-temperature applications, Infrared pyrometers for non-contact measurement

  • Actuators: SCR (thyristor) power controllers for electric heaters, Solid-state relays for on/off heating control, Proportional control valves for steam or thermal fluid

  • Complexity: Intermediate with challenges including Long thermal time constants making tuning difficult


Control Strategies for Temperature Control:

  • pid: Standard PID control with proportional, integral, and derivative terms tuned for the thermal process dynamics

  • cascade: Master temperature loop outputs to slave heater/cooler control loop for tighter control

  • ratio: Maintain temperature ratio between zones for gradient applications


Programming Fundamentals in Structured Text:

Variables:
- declaration: VAR / VAR_INPUT / VAR_OUTPUT / VAR_IN_OUT / VAR_GLOBAL sections
- initialization: Variables can be initialized at declaration: Counter : INT := 0;
- constants: VAR CONSTANT section for read-only values

Operators:
- arithmetic: + - * / MOD (modulo)
- comparison: = <> < > <= >=
- logical: AND OR XOR NOT

ControlStructures:
- if: IF condition THEN statements; ELSIF condition THEN statements; ELSE statements; END_IF;
- case: CASE selector OF value1: statements; value2: statements; ELSE statements; END_CASE;
- for: FOR index := start TO end BY step DO statements; END_FOR;

Best Practices for Structured Text:

  • Use meaningful variable names with consistent naming conventions

  • Initialize all variables at declaration to prevent undefined behavior

  • Use enumerated types for state machines instead of magic numbers

  • Break complex expressions into intermediate variables for readability

  • Use functions for reusable calculations and function blocks for stateful operations


Common Mistakes to Avoid:

  • Using = instead of := for assignment (= is comparison)

  • Forgetting semicolons at end of statements

  • Integer division truncation - use REAL for decimal results

  • Infinite loops from incorrect WHILE/REPEAT conditions


Typical Applications:

1. PID control: Directly applicable to Temperature Control
2. Recipe management: Related control patterns
3. Statistical calculations: Related control patterns
4. Data logging: Related control patterns

Understanding these fundamentals prepares you to implement effective Structured Text solutions for Temperature Control using Inovance InoProShop / AutoShop.

Implementing Temperature Control with Structured Text

Industrial temperature control systems use PLCs to regulate process temperatures in manufacturing, food processing, chemical processing, and other applications. These systems maintain precise temperature setpoints through heating and cooling control while ensuring product quality and energy efficiency.

This walkthrough demonstrates practical implementation using Inovance InoProShop / AutoShop and Structured Text programming.

System Requirements:

A typical Temperature Control implementation includes:

Input Devices (Sensors):
1. RTDs (PT100/PT1000) for high-accuracy measurements: Critical for monitoring system state
2. Thermocouples (J, K, T types) for high-temperature applications: Critical for monitoring system state
3. Infrared pyrometers for non-contact measurement: Critical for monitoring system state
4. Thermistors for fast response applications: Critical for monitoring system state
5. Thermal imaging cameras for surface temperature monitoring: Critical for monitoring system state

Output Devices (Actuators):
1. SCR (thyristor) power controllers for electric heaters: Primary control output
2. Solid-state relays for on/off heating control: Supporting control function
3. Proportional control valves for steam or thermal fluid: Supporting control function
4. Solenoid valves for cooling water or refrigerant: Supporting control function
5. Variable frequency drives for cooling fan control: Supporting control function

Control Equipment:

  • Electric resistance heaters (cartridge, band, strip)

  • Steam injection systems

  • Thermal fluid (hot oil) systems

  • Refrigeration and chiller systems


Control Strategies for Temperature Control:

  • pid: Standard PID control with proportional, integral, and derivative terms tuned for the thermal process dynamics

  • cascade: Master temperature loop outputs to slave heater/cooler control loop for tighter control

  • ratio: Maintain temperature ratio between zones for gradient applications


Implementation Steps:

Step 1: Characterize thermal system dynamics (time constants, dead time)

In InoProShop / AutoShop, characterize thermal system dynamics (time constants, dead time).

Step 2: Select appropriate sensor type and placement for representative measurement

In InoProShop / AutoShop, select appropriate sensor type and placement for representative measurement.

Step 3: Size heating and cooling capacity for worst-case load conditions

In InoProShop / AutoShop, size heating and cooling capacity for worst-case load conditions.

Step 4: Implement PID control with appropriate sample time (typically 10x faster than process time constant)

In InoProShop / AutoShop, implement pid control with appropriate sample time (typically 10x faster than process time constant).

Step 5: Add output limiting and anti-windup for safe operation

In InoProShop / AutoShop, add output limiting and anti-windup for safe operation.

Step 6: Program ramp/soak profiles if required

In InoProShop / AutoShop, program ramp/soak profiles if required.


Inovance Function Design:

InoProShop strongly favours function-block reuse via the Library Manager — Inovance ships standard libraries for motion, drives, HMI, OPC UA, and industry-specific applications (lithium-battery, EV, elevator). AutoShop reuse is open-coded via P-label subroutines. OEM machine-builders increasingly default to InoProShop / AM600 to access the FB libraries.

Common Challenges and Solutions:

1. Long thermal time constants making tuning difficult

  • Solution: Structured Text addresses this through Powerful for complex logic.


2. Transport delay (dead time) causing instability

  • Solution: Structured Text addresses this through Excellent code reusability.


3. Non-linear response at different temperature ranges

  • Solution: Structured Text addresses this through Compact code representation.


4. Sensor placement affecting measurement accuracy

  • Solution: Structured Text addresses this through Good for algorithms and calculations.


Safety Considerations:

  • Independent high-limit safety thermostats (redundant to PLC)

  • Watchdog timers for heater control validity

  • Safe-state definition on controller failure (heaters off)

  • Thermal fuse backup for runaway conditions

  • Proper ventilation for combustible atmospheres


Performance Metrics:

  • Task and I/O timing: Record minimum, average, and maximum values under a defined test load

  • Accuracy: Define an acceptable tolerance and compare it with calibrated reference measurements

  • Throughput: Count completed cycles over a fixed interval and record rejected or incomplete cycles

  • Fault response: Measure detection, safe-state, alarm, and recovery behavior for each test case

  • Resource use: Record memory, communications load, and diagnostic-buffer behavior

Inovance Diagnostic Tools:

InoProShop online mode with full POU monitoring and breakpoint debug,EtherCAT diagnostics page with topology and slave status,Trace tool for analogue / motion signal capture,OPC UA server diagnostics page,Modbus communication trace utility,AutoShop online mode for legacy AC800 / Easy series,Inovance HMI integrated diagnostics for HMI-PLC binding faults,Servo-drive panel diagnostics with InoProShop drive-monitor view,EtherCAT slave-firmware update tool,Project compare tool for change tracking

Use the monitoring and diagnostic functions available in your InoProShop / AutoShop version, and record the software, firmware, hardware, workload, and test procedure with every result.

Inovance Structured Text Example for Temperature Control

Illustrative Structured Text example for Temperature Control using Inovance terminology. Adapt the syntax to your InoProShop / AutoShop release, compile it, and verify it in an isolated test environment before use on equipment.

(* Inovance InoProShop / AutoShop - Temperature Control Control *)
(* Structured Text Implementation for Process Control *)
(* On InoProShop projects, conventions follow CODESYS / IEC norms — Pasca *)

PROGRAM PRG_TEMPERATURE_CONTROL_Control

VAR
    (* State Machine Variables *)
    eState : E_TEMPERATURE_CONTROL_States := IDLE;
    bEnable : BOOL := FALSE;
    bFaultActive : BOOL := FALSE;

    (* Timers *)
    tonDebounce : TON;
    tonProcessTimeout : TON;
    tonFeedbackCheck : TON;

    (* Counters *)
    ctuCycleCounter : CTU;

    (* Process Variables *)
    rThermocouplesKtypeJtype : REAL := 0.0;
    rHeatingelements : REAL := 0.0;
    rSetpoint : REAL := 100.0; (* Illustrative value; replace with a reviewed requirement *)
END_VAR

VAR CONSTANT
    (* Process Control Process Parameters *)
    C_DEBOUNCE_TIME : TIME := T#500MS;
    C_PROCESS_TIMEOUT : TIME := T#30S; (* Illustrative value; verify for the process *)
    C_BATCH_SIZE : INT := 50; (* Illustrative value; replace with a reviewed requirement *)
END_VAR

(* Input Conditioning *)
tonDebounce(IN := bStartButton, PT := C_DEBOUNCE_TIME);
bEnable := tonDebounce.Q AND NOT bEmergencyStop AND bSafetyOK;

(* Main State Machine - Pattern: InoProShop state machines typically use  *)
CASE eState OF
    IDLE:
        rHeatingelements := 0.0;
        ctuCycleCounter(RESET := TRUE);
        IF bEnable AND rThermocouplesKtypeJtype > 10.0 THEN
            eState := STARTING;
        END_IF;

    STARTING:
        (* Ramp up output - Gradual start *)
        rHeatingelements := MIN(rHeatingelements + 5.0, rSetpoint);
        IF rHeatingelements >= rSetpoint THEN
            eState := RUNNING;
        END_IF;

    RUNNING:
        (* Temperature Control active - Industrial temperature control systems use PLCs to *)
        tonProcessTimeout(IN := TRUE, PT := C_PROCESS_TIMEOUT);
        ctuCycleCounter(CU := bCyclePulse, PV := C_BATCH_SIZE);

        IF ctuCycleCounter.Q THEN
            eState := COMPLETE;
        ELSIF tonProcessTimeout.Q THEN
            bFaultActive := TRUE;
            eState := FAULT;
        END_IF;

    COMPLETE:
        rHeatingelements := 0.0;
        (* Log production data - InoProShop on AM600 / H5U supports SD-card logging via library FBs, plus OPC UA streaming for cloud / on-premises historians. Inovance HMIs add CSV logging at HMI tier. AutoShop projects rely on HMI-tier logging exclusively. *)
        eState := IDLE;

    FAULT:
        rHeatingelements := 0.0;
        (* InoProShop alarms are typically defined in the visualisation alarm-configuration page with severity, latching, and acknowledgement behaviour configured per alarm. The runtime maintains active and historical alarm lists. AutoShop projects fall back to M-flag banks with HMI-side alarm logging. *)
        IF bFaultReset AND NOT bEmergencyStop THEN
            bFaultActive := FALSE;
            eState := IDLE;
        END_IF;
END_CASE;

(* Safety Override - Always executes *)
IF bEmergencyStop OR NOT bSafetyOK THEN
    rHeatingelements := 0.0;
    eState := FAULT;
    bFaultActive := TRUE;
END_IF;

END_PROGRAM

Code Explanation:

  • 1.Enumerated state machine (InoProShop state machines typically use IEC SFC steps with action blocks per step, or a state-enum-and-CASE pattern in Structured Text. SFC dominates production-line sequencers; CASE patterns dominate axis-control state and recipe-routing logic. AutoShop projects fall back to FX-style SFC step memory (S0..S511) or D-register integer state.) for clear Temperature Control sequence control
  • 2.Constants use clearly marked illustrative values that must be replaced with reviewed project requirements
  • 3.Input conditioning with debounce timer prevents false triggers in industrial environment
  • 4.STARTING state implements soft-start ramp - prevents mechanical shock
  • 5.Process timeout detection flags a possible stuck condition for investigation
  • 6.The final override illustrates a software permissive only; it is not a safety-rated function and must not replace a validated safety system

Best Practices

  • Follow Inovance naming conventions: On InoProShop projects, conventions follow CODESYS / IEC norms — PascalCase for
  • Inovance function design: InoProShop strongly favours function-block reuse via the Library Manager — Inova
  • Data organization: InoProShop uses GVLs and persistent variables for shared data. AutoShop uses D /
  • Structured Text: Use meaningful variable names with consistent naming conventions
  • Structured Text: Initialize all variables at declaration to prevent undefined behavior
  • Structured Text: Use enumerated types for state machines instead of magic numbers
  • Temperature Control: Sample at 1/10 of the process time constant minimum
  • Temperature Control: Use derivative on PV, not error, for temperature control
  • Temperature Control: Start with conservative tuning and tighten gradually
  • Debug with InoProShop / AutoShop: Use InoProShop's online mode to set breakpoints in POUs and step throu
  • Safety: Independent high-limit safety thermostats (redundant to PLC)
  • Use a compatible simulator or isolated test rig to test Temperature Control logic before deployment

Common Pitfalls to Avoid

  • Structured Text: Using = instead of := for assignment (= is comparison)
  • Structured Text: Forgetting semicolons at end of statements
  • Structured Text: Integer division truncation - use REAL for decimal results
  • Inovance common error: EtherCAT slave order mismatch after physical re-cabling — slave addressing break
  • Temperature Control: Long thermal time constants making tuning difficult
  • Temperature Control: Transport delay (dead time) causing instability
  • Neglecting to validate RTDs (PT100/PT1000) for high-accuracy measurements leads to control errors
  • Insufficient comments make Structured Text programs unmaintainable over time

Related Certifications

🏆Inovance Certified Engineer
🏆InoProShop / AutoShop training certificates
🏆EV / Lithium Battery automation specialist tracks
🏆Advanced Inovance Programming Certification

Applying Structured Text to Temperature Control using Inovance InoProShop / AutoShop requires understanding the platform, the process, and the project's acceptance criteria. This guide has covered implementation structure, an illustrative code example, verification practices, and common pitfalls for a intermediate Temperature Control exercise.

Use the practices outlined here to create a design that can be reviewed and tested. Define performance targets in the project requirements and confirm them with repeatable measurements.

Next Steps:

1. Check Sources: Read the current InoProShop / AutoShop help, controller manual, release notes, and relevant standards
2. Practice Safely: Adapt the example in a simulator or isolated training setup
3. Review: Have the I/O map, state behavior, faults, and recovery steps reviewed
4. Test: Record normal, boundary, fault, restart, and communications test results

Structured Text Foundation:

Structured Text (ST) is a high-level, text-based programming language defined in IEC 61131-3. It resembles Pascal and provides powerful constructs for...

Project duration depends on scope, reviews, hardware availability, software and firmware versions, testing, commissioning, and site constraints. Remember: Sample at 1/10 of the process time constant minimum

For further learning, explore related topics including Recipe management, Plastic molding machines, and Inovance platform-specific features for Temperature Control optimization.