Learning to implement Function Blocks for Temperature Control using Inovance's InoProShop / AutoShop is a useful skill for PLC programmers working in Process Control. This guide walks through the fundamentals with clear explanations and an illustrative example that you can adapt to a simulator or test bench.
The example uses Inovance terminology and references controller families such as AM600 and AM610. Confirm the exact instructions, data types, firmware requirements, and licensing in the current vendor documentation before choosing hardware or deploying a project.
The Function Blocks approach is particularly well-suited for Temperature Control because process control, continuous operations, modular programming, and signal flow visualization. This combination allows you to leverage visual representation of signal flow while managing the typical challenges of Temperature Control, including pid tuning and temperature stability.
Throughout this guide, you'll find step-by-step implementation guidance, an illustrative code example, and a verification checklist specific to Process Control. Whether you're programming your first Temperature Control exercise or transitioning from another PLC platform, use the material as a starting point and validate it in your exact InoProShop / AutoShop version and controller environment.
Inovance InoProShop / AutoShop for Temperature Control
InoProShop / AutoShop is a programming environment associated with Inovance controller families such as AM600, AM610, H5U. This guide uses Function Blocks terminology from the supplied guide dataset, but controller capabilities and language support can change by model, firmware, software edition, and license.
Verify Before You Start:
- The selected controller supports the required Function Blocks constructs
- The project version matches the installed InoProShop / AutoShop release
- Required communications, motion, safety, and simulation options are licensed
- Firmware and device-description files are compatible with the project
- The vendor manuals used for the design match the exact hardware revision
Application Planning:
For a Temperature Control exercise, map the required inputs and outputs before writing logic. The example considers 4 sensor types, including Thermocouples (K-type, J-type), RTD sensors (PT100, PT1000), Infrared temperature sensors, and 5 actuator types.
Control Equipment for Temperature Control:
- Electric resistance heaters (cartridge, band, strip)
- Steam injection systems
- Thermal fluid (hot oil) systems
- Refrigeration and chiller systems
Controller-family references used in this guide include:
- AM600: Confirm CPU, I/O, memory, communications, and Function Blocks support in the current selection guide
- AM610: Confirm CPU, I/O, memory, communications, and Function Blocks support in the current selection guide
- H5U: Confirm CPU, I/O, memory, communications, and Function Blocks support in the current selection guide
- AC800: Confirm CPU, I/O, memory, communications, and Function Blocks support in the current selection guide
Hardware Selection Checklist:
- Count local and remote I/O, including planned expansion
- Measure the required task and communications update rates
- Identify memory, data-retention, diagnostics, and cybersecurity requirements
- Treat safety functions as a separate, standards-led design activity
- Confirm lifecycle status, regional availability, licensing, and support
Source and Validation Note:
This page does not represent a vendor certification or a hardware acceptance test. Use current Inovance manuals, release notes, and safety documentation as the authority for product-specific behavior. Validate adapted logic in a simulator or isolated test setup before connecting it to equipment.
Investment Considerations:
For Temperature Control projects, compare hardware, software licensing, training, engineering, test equipment, commissioning, spares, and ongoing support. Obtain current pricing and lifecycle information directly from the vendor or an authorized regional supplier.
Understanding Function Blocks for Temperature Control
Function Block Diagram (FBD) is a graphical programming language where functions and function blocks are represented as boxes connected by signal lines. Data flows from left to right through the network.
Execution Model:
Blocks execute based on data dependencies - a block executes only when all its inputs are available. Networks execute top to bottom when dependencies allow.
Core Advantages for Temperature Control:
- Visual representation of signal flow: Critical for Temperature Control when handling intermediate control logic
- Good for modular programming: Critical for Temperature Control when handling intermediate control logic
- Reusable components: Critical for Temperature Control when handling intermediate control logic
- Excellent for process control: Critical for Temperature Control when handling intermediate control logic
- Good for continuous operations: Critical for Temperature Control when handling intermediate control logic
Why Function Blocks Fits Temperature Control:
Temperature Control systems in Process Control typically involve:
- Sensors: RTDs (PT100/PT1000) for high-accuracy measurements, Thermocouples (J, K, T types) for high-temperature applications, Infrared pyrometers for non-contact measurement
- Actuators: SCR (thyristor) power controllers for electric heaters, Solid-state relays for on/off heating control, Proportional control valves for steam or thermal fluid
- Complexity: Intermediate with challenges including Long thermal time constants making tuning difficult
Control Strategies for Temperature Control:
- pid: Standard PID control with proportional, integral, and derivative terms tuned for the thermal process dynamics
- cascade: Master temperature loop outputs to slave heater/cooler control loop for tighter control
- ratio: Maintain temperature ratio between zones for gradient applications
Programming Fundamentals in Function Blocks:
StandardBlocks:
- logic: AND, OR, XOR, NOT - Boolean logic operations
- comparison: EQ, NE, LT, GT, LE, GE - Compare values
- math: ADD, SUB, MUL, DIV, MOD - Arithmetic operations
TimersCounters:
- ton: Timer On-Delay - Output turns ON after preset time
- tof: Timer Off-Delay - Output turns OFF after preset time
- tp: Pulse Timer - Output pulses for preset time
Connections:
- wires: Connect output pins to input pins to pass data
- branches: One output can connect to multiple inputs
- feedback: Outputs can feed back to inputs for state machines
Best Practices for Function Blocks:
- Arrange blocks for clear left-to-right data flow
- Use consistent spacing and alignment for readability
- Label all inputs and outputs with meaningful names
- Create custom FBs for frequently repeated logic patterns
- Minimize wire crossings by careful block placement
Common Mistakes to Avoid:
- Creating feedback loops without proper initialization
- Connecting incompatible data types
- Not considering execution order dependencies
- Overcrowding networks making them hard to read
Typical Applications:
1. HVAC control: Directly applicable to Temperature Control
2. Temperature control: Related control patterns
3. Flow control: Related control patterns
4. Batch processing: Related control patterns
Understanding these fundamentals prepares you to implement effective Function Blocks solutions for Temperature Control using Inovance InoProShop / AutoShop.
Implementing Temperature Control with Function Blocks
Industrial temperature control systems use PLCs to regulate process temperatures in manufacturing, food processing, chemical processing, and other applications. These systems maintain precise temperature setpoints through heating and cooling control while ensuring product quality and energy efficiency.
This walkthrough demonstrates practical implementation using Inovance InoProShop / AutoShop and Function Blocks programming.
System Requirements:
A typical Temperature Control implementation includes:
Input Devices (Sensors):
1. RTDs (PT100/PT1000) for high-accuracy measurements: Critical for monitoring system state
2. Thermocouples (J, K, T types) for high-temperature applications: Critical for monitoring system state
3. Infrared pyrometers for non-contact measurement: Critical for monitoring system state
4. Thermistors for fast response applications: Critical for monitoring system state
5. Thermal imaging cameras for surface temperature monitoring: Critical for monitoring system state
Output Devices (Actuators):
1. SCR (thyristor) power controllers for electric heaters: Primary control output
2. Solid-state relays for on/off heating control: Supporting control function
3. Proportional control valves for steam or thermal fluid: Supporting control function
4. Solenoid valves for cooling water or refrigerant: Supporting control function
5. Variable frequency drives for cooling fan control: Supporting control function
Control Equipment:
- Electric resistance heaters (cartridge, band, strip)
- Steam injection systems
- Thermal fluid (hot oil) systems
- Refrigeration and chiller systems
Control Strategies for Temperature Control:
- pid: Standard PID control with proportional, integral, and derivative terms tuned for the thermal process dynamics
- cascade: Master temperature loop outputs to slave heater/cooler control loop for tighter control
- ratio: Maintain temperature ratio between zones for gradient applications
Implementation Steps:
Step 1: Characterize thermal system dynamics (time constants, dead time)
In InoProShop / AutoShop, characterize thermal system dynamics (time constants, dead time).
Step 2: Select appropriate sensor type and placement for representative measurement
In InoProShop / AutoShop, select appropriate sensor type and placement for representative measurement.
Step 3: Size heating and cooling capacity for worst-case load conditions
In InoProShop / AutoShop, size heating and cooling capacity for worst-case load conditions.
Step 4: Implement PID control with appropriate sample time (typically 10x faster than process time constant)
In InoProShop / AutoShop, implement pid control with appropriate sample time (typically 10x faster than process time constant).
Step 5: Add output limiting and anti-windup for safe operation
In InoProShop / AutoShop, add output limiting and anti-windup for safe operation.
Step 6: Program ramp/soak profiles if required
In InoProShop / AutoShop, program ramp/soak profiles if required.
Inovance Function Design:
InoProShop strongly favours function-block reuse via the Library Manager — Inovance ships standard libraries for motion, drives, HMI, OPC UA, and industry-specific applications (lithium-battery, EV, elevator). AutoShop reuse is open-coded via P-label subroutines. OEM machine-builders increasingly default to InoProShop / AM600 to access the FB libraries.
Common Challenges and Solutions:
1. Long thermal time constants making tuning difficult
- Solution: Function Blocks addresses this through Visual representation of signal flow.
2. Transport delay (dead time) causing instability
- Solution: Function Blocks addresses this through Good for modular programming.
3. Non-linear response at different temperature ranges
- Solution: Function Blocks addresses this through Reusable components.
4. Sensor placement affecting measurement accuracy
- Solution: Function Blocks addresses this through Excellent for process control.
Safety Considerations:
- Independent high-limit safety thermostats (redundant to PLC)
- Watchdog timers for heater control validity
- Safe-state definition on controller failure (heaters off)
- Thermal fuse backup for runaway conditions
- Proper ventilation for combustible atmospheres
Performance Metrics:
- Task and I/O timing: Record minimum, average, and maximum values under a defined test load
- Accuracy: Define an acceptable tolerance and compare it with calibrated reference measurements
- Throughput: Count completed cycles over a fixed interval and record rejected or incomplete cycles
- Fault response: Measure detection, safe-state, alarm, and recovery behavior for each test case
- Resource use: Record memory, communications load, and diagnostic-buffer behavior
Inovance Diagnostic Tools:
InoProShop online mode with full POU monitoring and breakpoint debug,EtherCAT diagnostics page with topology and slave status,Trace tool for analogue / motion signal capture,OPC UA server diagnostics page,Modbus communication trace utility,AutoShop online mode for legacy AC800 / Easy series,Inovance HMI integrated diagnostics for HMI-PLC binding faults,Servo-drive panel diagnostics with InoProShop drive-monitor view,EtherCAT slave-firmware update tool,Project compare tool for change tracking
Use the monitoring and diagnostic functions available in your InoProShop / AutoShop version, and record the software, firmware, hardware, workload, and test procedure with every result.
Inovance Function Blocks Example for Temperature Control
Illustrative Function Blocks example for Temperature Control using Inovance terminology. Adapt the syntax to your InoProShop / AutoShop release, compile it, and verify it in an isolated test environment before use on equipment.
(* Inovance InoProShop / AutoShop - Temperature Control Control *)
(* Reusable Function Blocks Implementation *)
(* InoProShop strongly favours function-block reuse via the Lib *)
FUNCTION_BLOCK FB_TEMPERATURE_CONTROL_Controller
VAR_INPUT
bEnable : BOOL; (* Enable control *)
bReset : BOOL; (* Fault reset *)
rProcessValue : REAL; (* RTDs (PT100/PT1000) for high-accuracy measurements *)
rSetpoint : REAL := 100.0; (* Illustrative value; replace with a reviewed requirement *)
bEmergencyStop : BOOL; (* Safety input *)
END_VAR
VAR_OUTPUT
rControlOutput : REAL; (* SCR (thyristor) power controllers for electric heaters *)
bRunning : BOOL; (* Process active *)
bComplete : BOOL; (* Cycle complete *)
bFault : BOOL; (* Fault status *)
nFaultCode : INT; (* Diagnostic code *)
END_VAR
VAR
(* Internal Function Blocks *)
fbSafety : FB_SafetyMonitor; (* Safety logic *)
fbRamp : FB_RampGenerator; (* Soft start/stop *)
fbPID : FB_PIDController; (* Process control *)
fbDiag : FB_Diagnostics; (* InoProShop alarms are typically defined in the visualisation alarm-configuration page with severity, latching, and acknowledgement behaviour configured per alarm. The runtime maintains active and historical alarm lists. AutoShop projects fall back to M-flag banks with HMI-side alarm logging. *)
(* Internal State *)
eInternalState : E_ControlState;
tonWatchdog : TON;
END_VAR
(* Safety Monitor - Independent high-limit safety thermostats (redundant to PLC) *)
fbSafety(
Enable := bEnable,
EmergencyStop := bEmergencyStop,
ProcessValue := rProcessValue,
HighLimit := rSetpoint * 1.2,
LowLimit := rSetpoint * 0.1
);
(* Main Control Logic *)
IF fbSafety.SafeToRun THEN
(* Ramp Generator - Prevents startup surge *)
fbRamp(
Enable := bEnable,
TargetValue := rSetpoint,
RampRate := 20.0, (* Illustrative value; tune and verify for the process *)
CurrentValue => rSetpoint
);
(* PID Controller - [object Object] *)
fbPID(
Enable := fbRamp.InPosition,
ProcessValue := rProcessValue,
Setpoint := fbRamp.CurrentValue,
Kp := 1.0,
Ki := 0.1,
Kd := 0.05,
OutputMin := 0.0,
OutputMax := 100.0
);
rControlOutput := fbPID.Output;
bRunning := TRUE;
bFault := FALSE;
nFaultCode := 0;
ELSE
(* Safe State - Watchdog timers for heater control validity *)
rControlOutput := 0.0;
bRunning := FALSE;
bFault := NOT bEnable; (* Only fault if not intentional stop *)
nFaultCode := fbSafety.FaultCode;
END_IF;
(* Diagnostics - InoProShop on AM600 / H5U supports SD-card logging via library FBs, plus OPC UA streaming for cloud / on-premises historians. Inovance HMIs add CSV logging at HMI tier. AutoShop projects rely on HMI-tier logging exclusively. *)
fbDiag(
ProcessRunning := bRunning,
FaultActive := bFault,
ProcessValue := rProcessValue,
ControlOutput := rControlOutput
);
(* Watchdog - Detects frozen control *)
tonWatchdog(IN := bRunning AND NOT fbPID.OutputChanging, PT := T#10S);
IF tonWatchdog.Q THEN
bFault := TRUE;
nFaultCode := 99; (* Watchdog fault *)
END_IF;
(* Reset Logic *)
IF bReset AND NOT bEmergencyStop THEN
bFault := FALSE;
nFaultCode := 0;
fbDiag.ClearAlarms();
END_IF;
END_FUNCTION_BLOCKCode Explanation:
- 1.Encapsulated function block follows InoProShop strongly favours function-blo - reusable across Process Control projects
- 2.FB_SafetyMonitor illustrates status checks and high/low limits; it is not a certified safety function
- 3.FB_RampGenerator prevents startup issues common in Temperature Control systems
- 4.FB_PIDController tuned for Process Control: Kp=1.0, Ki=0.1
- 5.Watchdog timer illustrates one way to flag an unchanged output for diagnosis
- 6.Diagnostic function block enables InoProShop on AM600 / H5U supports SD-card logging via library FBs, plus OPC UA streaming for cloud / on-premises historians. Inovance HMIs add CSV logging at HMI tier. AutoShop projects rely on HMI-tier logging exclusively. and InoProShop alarms are typically defined in the visualisation alarm-configuration page with severity, latching, and acknowledgement behaviour configured per alarm. The runtime maintains active and historical alarm lists. AutoShop projects fall back to M-flag banks with HMI-side alarm logging.
Best Practices
- ✓Follow Inovance naming conventions: On InoProShop projects, conventions follow CODESYS / IEC norms — PascalCase for
- ✓Inovance function design: InoProShop strongly favours function-block reuse via the Library Manager — Inova
- ✓Data organization: InoProShop uses GVLs and persistent variables for shared data. AutoShop uses D /
- ✓Function Blocks: Arrange blocks for clear left-to-right data flow
- ✓Function Blocks: Use consistent spacing and alignment for readability
- ✓Function Blocks: Label all inputs and outputs with meaningful names
- ✓Temperature Control: Sample at 1/10 of the process time constant minimum
- ✓Temperature Control: Use derivative on PV, not error, for temperature control
- ✓Temperature Control: Start with conservative tuning and tighten gradually
- ✓Debug with InoProShop / AutoShop: Use InoProShop's online mode to set breakpoints in POUs and step throu
- ✓Safety: Independent high-limit safety thermostats (redundant to PLC)
- ✓Use a compatible simulator or isolated test rig to test Temperature Control logic before deployment
Common Pitfalls to Avoid
- ⚠Function Blocks: Creating feedback loops without proper initialization
- ⚠Function Blocks: Connecting incompatible data types
- ⚠Function Blocks: Not considering execution order dependencies
- ⚠Inovance common error: EtherCAT slave order mismatch after physical re-cabling — slave addressing break
- ⚠Temperature Control: Long thermal time constants making tuning difficult
- ⚠Temperature Control: Transport delay (dead time) causing instability
- ⚠Neglecting to validate RTDs (PT100/PT1000) for high-accuracy measurements leads to control errors
- ⚠Insufficient comments make Function Blocks programs unmaintainable over time
Related Certifications
Applying Function Blocks to Temperature Control using Inovance InoProShop / AutoShop requires understanding the platform, the process, and the project's acceptance criteria. This guide has covered implementation structure, an illustrative code example, verification practices, and common pitfalls for a intermediate Temperature Control exercise.
Use the practices outlined here to create a design that can be reviewed and tested. Define performance targets in the project requirements and confirm them with repeatable measurements.
Next Steps:
1. Check Sources: Read the current InoProShop / AutoShop help, controller manual, release notes, and relevant standards
2. Practice Safely: Adapt the example in a simulator or isolated training setup
3. Review: Have the I/O map, state behavior, faults, and recovery steps reviewed
4. Test: Record normal, boundary, fault, restart, and communications test results
Function Blocks Foundation:
Function Block Diagram (FBD) is a graphical programming language where functions and function blocks are represented as boxes connected by signal line...
Project duration depends on scope, reviews, hardware availability, software and firmware versions, testing, commissioning, and site constraints. Remember: Sample at 1/10 of the process time constant minimum
For further learning, explore related topics including Temperature control, Plastic molding machines, and Inovance platform-specific features for Temperature Control optimization.