Learn PLCs free
Intermediate25 min readPackaging

Mitsubishi Structured Text for Bottle Filling

Learn Structured Text programming for Bottle Filling using Mitsubishi GX Works2/GX Works3. Includes code examples, best practices, and step-by-step implementation guide for Packaging applications.

💻
Platform
GX Works2/GX Works3
📊
Complexity
Intermediate to Advanced
⏱️
Project Duration
3-6 weeks

Advanced Structured Text techniques for Bottle Filling in Mitsubishi's GX Works2/GX Works3 can improve code organization, diagnostics, and reuse when they are applied deliberately. This guide explores patterns that go beyond a basic implementation and explains how to evaluate their tradeoffs.

Available language features and libraries depend on the controller family, firmware, installed options, and GX Works2/GX Works3 version. Confirm each feature in current vendor documentation and create a minimal compile-and-run test before incorporating it into a larger project.

Advanced Bottle Filling implementations leverage sophisticated techniques including multi-sensor fusion algorithms, coordinated multi-actuator control, and intelligent handling of precise fill volume. When implemented using Structured Text, these capabilities are achieved through complex calculations patterns that exploit Mitsubishi-specific optimizations.

This guide examines custom function blocks, data structures, advanced Structured Text patterns, and version-dependent GX Works2/GX Works3 features. For each technique, assess readability, scan-time cost, failure behavior, portability, and how the design will be tested and maintained.

Mitsubishi GX Works2/GX Works3 for Bottle Filling

GX Works2/GX Works3 is a programming environment associated with Mitsubishi controller families such as FX5, iQ-R, iQ-F. This guide uses Structured Text terminology from the supplied guide dataset, but controller capabilities and language support can change by model, firmware, software edition, and license.

Verify Before You Start:

  • The selected controller supports the required Structured Text constructs

  • The project version matches the installed GX Works2/GX Works3 release

  • Required communications, motion, safety, and simulation options are licensed

  • Firmware and device-description files are compatible with the project

  • The vendor manuals used for the design match the exact hardware revision


Application Planning:

For a Bottle Filling exercise, map the required inputs and outputs before writing logic. The example considers 5 sensor types, including Level sensors, Flow meters, Pressure sensors, and 5 actuator types.

Control Equipment for Bottle Filling:

  • Filling nozzles (gravity, pressure, vacuum)

  • Product tanks with level control

  • CIP (clean-in-place) systems

  • Cap feeding and sorting equipment


Controller-family references used in this guide include:

  • FX5: Confirm CPU, I/O, memory, communications, and Structured Text support in the current selection guide

  • iQ-R: Confirm CPU, I/O, memory, communications, and Structured Text support in the current selection guide

  • iQ-F: Confirm CPU, I/O, memory, communications, and Structured Text support in the current selection guide

  • Q Series: Confirm CPU, I/O, memory, communications, and Structured Text support in the current selection guide


Hardware Selection Checklist:

  • Count local and remote I/O, including planned expansion

  • Measure the required task and communications update rates

  • Identify memory, data-retention, diagnostics, and cybersecurity requirements

  • Treat safety functions as a separate, standards-led design activity

  • Confirm lifecycle status, regional availability, licensing, and support


Source and Validation Note:

This page does not represent a vendor certification or a hardware acceptance test. Use current Mitsubishi manuals, release notes, and safety documentation as the authority for product-specific behavior. Validate adapted logic in a simulator or isolated test setup before connecting it to equipment.

Investment Considerations:

For Bottle Filling projects, compare hardware, software licensing, training, engineering, test equipment, commissioning, spares, and ongoing support. Obtain current pricing and lifecycle information directly from the vendor or an authorized regional supplier.

Understanding Structured Text for Bottle Filling

Structured Text (ST) is a high-level, text-based programming language defined in IEC 61131-3. It resembles Pascal and provides powerful constructs for complex algorithms, calculations, and data manipulation.

Execution Model:

Code executes sequentially from top to bottom within each program unit. Variables maintain state between scan cycles unless explicitly reset.

Core Advantages for Bottle Filling:

  • Powerful for complex logic: Critical for Bottle Filling when handling intermediate to advanced control logic

  • Excellent code reusability: Critical for Bottle Filling when handling intermediate to advanced control logic

  • Compact code representation: Critical for Bottle Filling when handling intermediate to advanced control logic

  • Good for algorithms and calculations: Critical for Bottle Filling when handling intermediate to advanced control logic

  • Familiar to software developers: Critical for Bottle Filling when handling intermediate to advanced control logic


Why Structured Text Fits Bottle Filling:

Bottle Filling systems in Packaging typically involve:

  • Sensors: Bottle presence sensors (fiber optic or inductive) for container detection, Level sensors (capacitive, ultrasonic, or optical) for fill detection, Load cells for gravimetric (weight-based) filling

  • Actuators: Servo-driven filling valves for precise flow control, Pneumatic pinch valves for on/off flow control, Bottle handling star wheels and timing screws

  • Complexity: Intermediate to Advanced with challenges including Preventing dripping and stringing after fill cutoff


Programming Fundamentals in Structured Text:

Variables:
- declaration: VAR / VAR_INPUT / VAR_OUTPUT / VAR_IN_OUT / VAR_GLOBAL sections
- initialization: Variables can be initialized at declaration: Counter : INT := 0;
- constants: VAR CONSTANT section for read-only values

Operators:
- arithmetic: + - * / MOD (modulo)
- comparison: = <> < > <= >=
- logical: AND OR XOR NOT

ControlStructures:
- if: IF condition THEN statements; ELSIF condition THEN statements; ELSE statements; END_IF;
- case: CASE selector OF value1: statements; value2: statements; ELSE statements; END_CASE;
- for: FOR index := start TO end BY step DO statements; END_FOR;

Best Practices for Structured Text:

  • Use meaningful variable names with consistent naming conventions

  • Initialize all variables at declaration to prevent undefined behavior

  • Use enumerated types for state machines instead of magic numbers

  • Break complex expressions into intermediate variables for readability

  • Use functions for reusable calculations and function blocks for stateful operations


Common Mistakes to Avoid:

  • Using = instead of := for assignment (= is comparison)

  • Forgetting semicolons at end of statements

  • Integer division truncation - use REAL for decimal results

  • Infinite loops from incorrect WHILE/REPEAT conditions


Typical Applications:

1. PID control: Directly applicable to Bottle Filling
2. Recipe management: Related control patterns
3. Statistical calculations: Related control patterns
4. Data logging: Related control patterns

Understanding these fundamentals prepares you to implement effective Structured Text solutions for Bottle Filling using Mitsubishi GX Works2/GX Works3.

Implementing Bottle Filling with Structured Text

Bottle filling control systems manage the precise dispensing of liquids into containers at high speeds while maintaining accuracy and preventing spillage. PLCs coordinate container handling, fill control, capping, and quality inspection in an integrated packaging line.

This walkthrough demonstrates practical implementation using Mitsubishi GX Works2/GX Works3 and Structured Text programming.

System Requirements:

A typical Bottle Filling implementation includes:

Input Devices (Sensors):
1. Bottle presence sensors (fiber optic or inductive) for container detection: Critical for monitoring system state
2. Level sensors (capacitive, ultrasonic, or optical) for fill detection: Critical for monitoring system state
3. Load cells for gravimetric (weight-based) filling: Critical for monitoring system state
4. Flow meters (magnetic or mass flow) for volumetric filling: Critical for monitoring system state
5. Encoder feedback for rotary filler position: Critical for monitoring system state

Output Devices (Actuators):
1. Servo-driven filling valves for precise flow control: Primary control output
2. Pneumatic pinch valves for on/off flow control: Supporting control function
3. Bottle handling star wheels and timing screws: Supporting control function
4. Capping chuck drives (servo or pneumatic): Supporting control function
5. Torque limiters for cap tightening: Supporting control function

Control Equipment:

  • Filling nozzles (gravity, pressure, vacuum)

  • Product tanks with level control

  • CIP (clean-in-place) systems

  • Cap feeding and sorting equipment


Control Strategies for Bottle Filling:

1. Primary Control: Automated bottle filling and capping systems using PLCs for precise volume control, speed optimization, and quality assurance.
2. Safety Interlocks: Preventing Precise fill volume
3. Error Recovery: Handling High-speed operation

Implementation Steps:

Step 1: Characterize product flow properties (viscosity, foaming, temperature sensitivity)

In GX Works2/GX Works3, characterize product flow properties (viscosity, foaming, temperature sensitivity).

Step 2: Determine fill method based on accuracy requirements and product type

In GX Works2/GX Works3, determine fill method based on accuracy requirements and product type.

Step 3: Design container handling for smooth, jam-free operation

In GX Works2/GX Works3, design container handling for smooth, jam-free operation.

Step 4: Implement fill sequence with proper valve timing and deceleration

In GX Works2/GX Works3, implement fill sequence with proper valve timing and deceleration.

Step 5: Add bulk/dribble transition logic for gravimetric filling

In GX Works2/GX Works3, add bulk/dribble transition logic for gravimetric filling.

Step 6: Program calibration routines for automatic fill adjustment

In GX Works2/GX Works3, program calibration routines for automatic fill adjustment.


Mitsubishi Function Design:

Function block (FB) programming in Mitsubishi creates reusable logic modules with defined interfaces encapsulating complexity. FB definition includes input variables (VAR_INPUT), output variables (VAR_OUTPUT), internal variables (VAR), and retained variables (VAR_RETAIN) maintaining values between calls. Creating motor control FB: inputs include Start_Cmd (BOOL), Stop_Cmd (BOOL), Speed_SP (INT), outputs include Running_Sts (BOOL), Fault_Sts (BOOL), Actual_Speed (INT), internal variables store timers, state machine stages, and diagnostic counters. FB instantiation creates instance: Motor1 (Motor_FB) with unique variable storage, allowing multiple instances Motor1, Motor2, Motor3 controlling different motors using same logic. Array of FB instances: Motors : ARRAY[1..10] OF Motor_FB accessed as Motors[3].Running_Sts checking status of motor 3. Standard function (FUN) differs from FB by lacking internal memory, suitable for calculations or conversions: Temp_Conversion_FUN(Celsius) returns Fahrenheit without retaining historical data. Structured text programming within FBs/FUNs provides clearer logic for complex algorithms compared to ladder: IF-THEN-ELSIF-ELSE structures, FOR loops, CASE statements expressing intent more directly than ladder equivalents. EN/ENO functionality enables conditional execution: EN (enable input) controls whether FB executes, ENO (enable output) indicates successful execution detecting errors within block. Library management exports FBs to library files (.glib) shared across projects and engineering teams, versioned to track modifications and ensure consistency. The intelligent function module (IFM) templates provide pre-built FBs for common applications: PID control, analog scaling, motion positioning reducing development time and providing tested reliable code. Simulation mode tests FB logic without hardware, allowing desktop development and unit testing before commissioning. Protection functionality encrypts FB contents preventing unauthorized viewing or modification, useful for proprietary algorithms or OEM machine builders distributing programs to end users.

Common Challenges and Solutions:

1. Preventing dripping and stringing after fill cutoff

  • Solution: Structured Text addresses this through Powerful for complex logic.


2. Handling foaming products that give false level readings

  • Solution: Structured Text addresses this through Excellent code reusability.


3. Maintaining accuracy at high speeds

  • Solution: Structured Text addresses this through Compact code representation.


4. Synchronizing multi-head rotary fillers

  • Solution: Structured Text addresses this through Good for algorithms and calculations.


Safety Considerations:

  • Guarding around rotating components

  • Interlocked access doors with safe stop

  • Bottle breakage detection and containment

  • Overpressure protection for pressure filling

  • Chemical handling safety for cleaning solutions


Performance Metrics:

  • Task and I/O timing: Record minimum, average, and maximum values under a defined test load

  • Accuracy: Define an acceptable tolerance and compare it with calibrated reference measurements

  • Throughput: Count completed cycles over a fixed interval and record rejected or incomplete cycles

  • Fault response: Measure detection, safe-state, alarm, and recovery behavior for each test case

  • Resource use: Record memory, communications load, and diagnostic-buffer behavior

Mitsubishi Diagnostic Tools:

Device memory monitor: Real-time table displaying current values for X, Y, M, D devices with force capability,Entry data monitor: Shows actual rung logic states with contact ON/OFF indication during program execution,Device test: Manually control outputs and set internal relays for wiring verification without program influence,Intelligent module diagnostics: Buffer memory display showing module status, error codes, and configuration,Scan time monitor: Displays current, maximum, and minimum scan times identifying performance issues,Error code history: Chronological log of system errors, module faults, and CPU events with timestamps,CC-Link/network diagnostics: Visual network status showing connected stations, errors, and communication statistics,SD card operation log: Records all SD card read/write operations, file transfers, and access timestamps,Remote diagnosis via Ethernet: Connect GX Works over network for monitoring and troubleshooting without local access,Sampling trace: Records device value changes over time with trigger conditions for intermittent fault analysis,System monitor: Displays CPU load, memory usage, and battery status for predictive maintenance,Safety diagnosis (safety CPU): Dedicated diagnostics for safety I/O discrepancy detection and emergency stop chain status

Use the monitoring and diagnostic functions available in your GX Works2/GX Works3 version, and record the software, firmware, hardware, workload, and test procedure with every result.

Mitsubishi Structured Text Example for Bottle Filling

Illustrative Structured Text example for Bottle Filling using Mitsubishi terminology. Adapt the syntax to your GX Works2/GX Works3 release, compile it, and verify it in an isolated test environment before use on equipment.

(* Mitsubishi GX Works2/GX Works3 - Bottle Filling Control *)
(* Structured Text Implementation for Packaging *)
(* Mitsubishi programming supports both traditional device addressing (M0 *)

PROGRAM PRG_BOTTLE_FILLING_Control

VAR
    (* State Machine Variables *)
    eState : E_BOTTLE_FILLING_States := IDLE;
    bEnable : BOOL := FALSE;
    bFaultActive : BOOL := FALSE;

    (* Timers *)
    tonDebounce : TON;
    tonProcessTimeout : TON;
    tonFeedbackCheck : TON;

    (* Counters *)
    ctuCycleCounter : CTU;

    (* Process Variables *)
    rLevelsensors : REAL := 0.0;
    rServomotors : REAL := 0.0;
    rSetpoint : REAL := 100.0; (* Illustrative value; replace with a reviewed requirement *)
END_VAR

VAR CONSTANT
    (* Packaging Process Parameters *)
    C_DEBOUNCE_TIME : TIME := T#500MS;
    C_PROCESS_TIMEOUT : TIME := T#30S; (* Illustrative value; verify for the process *)
    C_BATCH_SIZE : INT := 50; (* Illustrative value; replace with a reviewed requirement *)
END_VAR

(* Input Conditioning *)
tonDebounce(IN := bStartButton, PT := C_DEBOUNCE_TIME);
bEnable := tonDebounce.Q AND NOT bEmergencyStop AND bSafetyOK;

(* Main State Machine - Pattern: State machine implementation in Mitsubis *)
CASE eState OF
    IDLE:
        rServomotors := 0.0;
        ctuCycleCounter(RESET := TRUE);
        IF bEnable AND rLevelsensors > 0.0 THEN
            eState := STARTING;
        END_IF;

    STARTING:
        (* Ramp up output - Gradual start *)
        rServomotors := MIN(rServomotors + 5.0, rSetpoint);
        IF rServomotors >= rSetpoint THEN
            eState := RUNNING;
        END_IF;

    RUNNING:
        (* Bottle Filling active - Bottle filling control systems manage the precise  *)
        tonProcessTimeout(IN := TRUE, PT := C_PROCESS_TIMEOUT);
        ctuCycleCounter(CU := bCyclePulse, PV := C_BATCH_SIZE);

        IF ctuCycleCounter.Q THEN
            eState := COMPLETE;
        ELSIF tonProcessTimeout.Q THEN
            bFaultActive := TRUE;
            eState := FAULT;
        END_IF;

    COMPLETE:
        rServomotors := 0.0;
        (* Log production data - High-speed data logging in Mitsubishi uses file registers (R devices) organized as circular buffers with automatic SD card archiving for long-term storage. Create logging structure: file registers R0-R9999 storing 10,000 samples with each sample containing timestamp (R[base]), values (R[base+1] to R[base+10]), status (R[base+11]). Write pointer (D500) increments with each log entry: [MOV current time R[(D500*12)]] [MOV process values R[(D500*12)+1]] [INC D500] with modulo operation wrapping pointer [LD> D500 K9999] [MOV K0 D500]. Triggered logging initiates capture on alarm conditions preserving pre-trigger buffer: maintain continuous logging but flag trigger index enabling post-event retrieval of 100 samples before alarm and 500 samples after providing failure context. CSV file export uses SD card write instructions formatting file register data into comma-delimited text files readable by Excel or data analysis software: SDWR instruction writes R0-R9999 to SD:\LOG\data.csv with timestamp filename generation creating unique files daily. Sampling rates configurable from 10ms (fixed cycle interrupt program) to several minutes (main program logic) depending on process dynamics and storage capacity requirements. Data compression implements deadband filtering: log sample only when value changes exceed threshold reducing storage requirements for slowly-changing process variables like tank levels or temperatures. Integration with SCADA/historian systems uses SLMP protocol transferring logged data via Ethernet to centralized databases with automatic retry logic handling network interruptions preventing data loss. Batch correlation links production data to specific product lots: each batch start creates new log file section with batch ID header enabling traceability from raw materials through finished goods. Energy logging totalizes consumption from power meters connected via CC-Link or Modbus calculating specific energy per produced unit, identifying efficiency improvements and cost allocation by product line. Safety event logging captures all safety input states, bypass activations, and emergency stop events with tamper-proof timestamps meeting regulatory documentation requirements for incident investigations and compliance audits. *)
        eState := IDLE;

    FAULT:
        rServomotors := 0.0;
        (* Alarm management in Mitsubishi uses bit devices (M or B) for alarm active flags with corresponding data registers storing timestamps, values, and alarm details. Alarm structure allocates device ranges: M1000-M1999 for alarm active flags (1000 unique alarms), D5000-D5999 storing alarm timestamps or associated values. Alarm detection logic: [LD Tank_Level > High_Limit] [AND NOT previous alarm state M1000] [OUT M1000] [MOV current time D5000] capturing alarm activation moment. Alarm acknowledgment requires operator action via HMI: GOT screen button writes to acknowledgment bit (M2000) which resets alarm flag when condition clears [LD M1000] [AND alarm cleared] [AND M2000 acknowledged] [RST M1000] [RST M2000]. Priority classification uses different device ranges or separate bits: Critical alarms M1000-M1099, Warnings M1100-M1199, Information M1200-M1299 with severity-specific visual/audible HMI indicators. Alarm logging to SD card uses CSV file write instructions (SDWR) recording alarm number, timestamp, activation/deactivation, and associated process values for historical analysis and regulatory compliance. First-out alarm detection latches initial alarm in cascade of related faults: bearing temperature alarm (M1050) latches before motor overload (M1051) before production stopped (M1052) with reset sequence clearing in reverse order after root cause addressed. Integration with GOT HMI alarm viewer displays active alarms in sortable/filterable list with acknowledgment tracking, alarm help text, and corrective action guidance displayed to operators. Alarm rate limiting prevents flooding when single fault triggers hundreds of consequential alarms: introduce 5-second delays before enabling secondary alarms allowing operators to focus on root cause. Email notification for critical alarms uses Ethernet communication function blocks sending SMTP messages to distribution lists with alarm details formatted in message body. Statistical alarm analysis counts alarm frequencies storing totals in file registers: most frequent alarm identification guides preventive maintenance priorities addressing chronic equipment issues before failures occur. *)
        IF bFaultReset AND NOT bEmergencyStop THEN
            bFaultActive := FALSE;
            eState := IDLE;
        END_IF;
END_CASE;

(* Safety Override - Always executes *)
IF bEmergencyStop OR NOT bSafetyOK THEN
    rServomotors := 0.0;
    eState := FAULT;
    bFaultActive := TRUE;
END_IF;

END_PROGRAM

Code Explanation:

  • 1.Enumerated state machine (State machine implementation in Mitsubishi typically uses data registers (D devices) storing current state values with ladder logic evaluating state transitions. Define state constants using file registers or direct values: STATE_IDLE = 0, STATE_STARTING = 10, STATE_RUNNING = 20, STATE_STOPPING = 30, STATE_FAULT = 90 with spaced values allowing future state insertion. Current state stored in D0 with comparison instructions (LD= D0 K0) checking states and advancement logic incrementing or setting new state values (MOV K10 D0). Timer-based state transitions use timer completion contacts: [TON timer T0 reaches preset] [AND current state = STARTING] [THEN advance to RUNNING state MOV K20 D0]. Structured text programming within function blocks provides clearer state machine logic: CASE Machine_State OF 0: (IDLE state actions and transition evaluation), 10: (STARTING state actions), 20: (RUNNING state actions), END_CASE. State transition logging writes state changes to file registers creating audit trail: when D0 changes, copy timestamp and previous state to R[pointer] incrementing pointer for circular buffer. Fault handling sets state to FAULT (90) with fault code stored in separate register (D10) indicating cause: 100=Emergency_Stop, 101=Overload, 102=Communication_Loss, with reset logic evaluating fault code and returning to appropriate safe state. Parallel state machines coordinate through shared status bits: Machine1_State (D100), Machine2_State (D200) with interlock logic preventing conflicting operations. HMI integration displays state names using text switching on D0 value converting numeric states to operator-friendly descriptions: 0='Ready', 10='Starting', 20='Running'. Function block encapsulation creates reusable state machine logic instantiated multiple times for identical equipment with instance-specific state storage in FB internal variables.) for clear Bottle Filling sequence control
  • 2.Constants use clearly marked illustrative values that must be replaced with reviewed project requirements
  • 3.Input conditioning with debounce timer prevents false triggers in industrial environment
  • 4.STARTING state implements soft-start ramp - prevents mechanical shock
  • 5.Process timeout detection flags a possible stuck condition for investigation
  • 6.The final override illustrates a software permissive only; it is not a safety-rated function and must not replace a validated safety system

Best Practices

  • Follow Mitsubishi naming conventions: Mitsubishi programming supports both traditional device addressing (M0, D100, X1
  • Mitsubishi function design: Function block (FB) programming in Mitsubishi creates reusable logic modules wit
  • Data organization: Mitsubishi uses file registers (R devices) and structured data in function block
  • Structured Text: Use meaningful variable names with consistent naming conventions
  • Structured Text: Initialize all variables at declaration to prevent undefined behavior
  • Structured Text: Use enumerated types for state machines instead of magic numbers
  • Bottle Filling: Use minimum 10 readings for statistical fill tracking
  • Bottle Filling: Implement automatic re-zero of scales at regular intervals
  • Bottle Filling: Provide separate parameters for each product recipe
  • Debug with GX Works2/GX Works3: Use sampling trace to capture high-speed events occurring faster than
  • Safety: Guarding around rotating components
  • Use a compatible simulator or isolated test rig to test Bottle Filling logic before deployment

Common Pitfalls to Avoid

  • Structured Text: Using = instead of := for assignment (= is comparison)
  • Structured Text: Forgetting semicolons at end of statements
  • Structured Text: Integer division truncation - use REAL for decimal results
  • Mitsubishi common error: Error 2110: Illegal device specified - accessing device outside configured range
  • Bottle Filling: Preventing dripping and stringing after fill cutoff
  • Bottle Filling: Handling foaming products that give false level readings
  • Neglecting to validate Bottle presence sensors (fiber optic or inductive) for container detection leads to control errors
  • Insufficient comments make Structured Text programs unmaintainable over time

Related Certifications

🏆Mitsubishi PLC Programming Certification
🏆Advanced Mitsubishi Programming Certification

Applying Structured Text to Bottle Filling using Mitsubishi GX Works2/GX Works3 requires understanding the platform, the process, and the project's acceptance criteria. This guide has covered implementation structure, an illustrative code example, verification practices, and common pitfalls for a intermediate to advanced Bottle Filling exercise.

Use the practices outlined here to create a design that can be reviewed and tested. Define performance targets in the project requirements and confirm them with repeatable measurements.

Next Steps:

1. Check Sources: Read the current GX Works2/GX Works3 help, controller manual, release notes, and relevant standards
2. Practice Safely: Adapt the example in a simulator or isolated training setup
3. Review: Have the I/O map, state behavior, faults, and recovery steps reviewed
4. Test: Record normal, boundary, fault, restart, and communications test results

Structured Text Foundation:

Structured Text (ST) is a high-level, text-based programming language defined in IEC 61131-3. It resembles Pascal and provides powerful constructs for...

Project duration depends on scope, reviews, hardware availability, software and firmware versions, testing, commissioning, and site constraints. Remember: Use minimum 10 readings for statistical fill tracking

For further learning, explore related topics including Recipe management, Pharmaceutical liquid filling, and Mitsubishi platform-specific features for Bottle Filling optimization.